ProgUSA has supplied electrical test and measurement equipment to utilities, NETA firms, and industrial users since 2005, including DV Power instruments for on-load tap changer diagnostics. The on-load tap changer (OLTC) is the only part of a power transformer that moves in normal operation. It switches under load while the windings and core stay still, and it accounts for a large share of transformer failures.


Static Testing and Its Blind Spot

Static winding resistance measurement (SRM) records resistance at each tap position while the tap changer is stationary. It is an effective check of winding continuity and contact integrity in a fixed position.

Its limitation is structural: it measures only what is in the circuit at the instant the reading is taken. The transition resistor is the clearest example. It carries current only while the diverter switch is in motion; at rest, it is not connected at all. A damaged or open transition resistor therefore passes a static test, because the faulty component is not in the measured path. The same is true of slow transitions and momentary open circuits during switching.


How Dynamic Resistance Measurement Works

Dynamic resistance measurement (DRM) is an offline, non-intrusive test that reaches the switching transition static testing cannot. A DC test current is injected through the winding while the tap changer runs through its positions, and the resulting current signature is recorded continuously against time. Depending on the instrument and method, that signature is analyzed as a dynamic resistance response, giving the complete behavior of each transition rather than a single value per tap.

DRM uses the same lead connection as static winding resistance measurement, so both tests run from one setup. Two parameters carry most of the diagnostic weight. Transition time, how long the diverter switch takes to operate, lengthens with weakening spring energy, mechanical binding, or a drive-train problem. Ripple, the variation in the trace while contacts move, reveals pitting, coking, and misalignment long before a static reading would. Through these signatures, DRM detects contact wear, synchronization issues, transition resistor degradation, slow transitions, and open circuits.


DRM and IEEE C57.152

DV Power ties dynamic resistance measurement to the updated IEEE C57.152 guide for diagnostic field testing of power transformers. Their point is simple. A static resistance reading tells you what the contacts measure at rest. DRM captures the OLTC contact transition itself, on a millisecond timescale, and that is where tap changer problems show up. 

Recording resolution is 0.1 ms, a 10 kHz sampling rate. Switching events are brief enough that a slower recorder averages them away.


DV Power Instruments for DRM

ProgUSA supplies the DV Power RMO-T and TWA Advanced series for dynamic resistance measurement. Both perform in-tank testing of tap changers, with no need to drain oil or open the tap-changer compartment.

Both static and dynamic resistance run from one setup, recording at 0.1 ms resolution. DV-TR software generates reports documenting each OLTC’s condition over time.


ProgUSA Support

ProgUSA backs the DV Power transformer test line with support, training and service in the United States.

Equipment Selection

We help utilities match the right winding resistance meter and tap changer analyzer to their transformer fleet and testing program.

Training

We provide training on test procedures, DRM interpretation, and software reporting.

Service and Calibration

We coordinate calibration and repair support for DV Power instruments in the United States.

Demonstrations

On-site demonstrations let crews run DRM on their own equipment. 


Learn More

The DV Power RMO-T and TWA Advanced series are available through ProgUSA, listed under Transformer & Winding Test. 

Request a quote or demonstration → 


ProgUSA | https://www.progusa.net/transformer-winding-test | info@progusa.net | +1 407 332 8678

in News